AMPACITIES OF NOT MORE THAN 3 INSULATED CONDUCTORS RATED 0-2, 000 VOLTS IN RACEWAY OR CABLE | |||
I N RACEWAY, CABLE, OR EARTH BASED CN AMBIENT TEMPERATURE OF 30°C (86°F) | |||
SIZE | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) |
AWG kcmil |
TYPES TW, UF |
TYPES RHW, THHW, THW, THWN, XHHW, USE, ZW |
TYPES TBS, SA, SIS. FEP, FEPB, Ml, RHH, RHW-2. THHN, THHW. THW-2.THWN-2. USE-2 XHH. XHHW, XHHW-2, ZW-2 |
14* 12* 10* 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 |
20 25 30 40 55 70 85 95 110 125 145 165 195 215 240 260 280 320 |
20 25 35 50 65 85 100 115 130 150 175 200 230 255 285 310 335 380 |
25 30 40 55 75 95 110 130 150 170 195 225 260 290 320 350 380 430 |
Overcurrent protection for conductor sizes marked (') shall not exceed 15 amperes for No. 14, 20 amperes for No, 12. and 30 amperes for No. 10 copper. See NEC 240-2 for motor & welders overcurrent protection exceptions. See NEC 240. |
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING | |||||||||||
Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
8 6 5 2 |
15 11 8 5 |
25 19 14 8 |
43 33 24 13 |
58 45 33 18 |
96 74 55 30 |
168 129 96 53 |
254 195 145 81 |
332 255 190 105 |
424 326 243 135 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
6 4 3 1 |
10 8 6 4 |
18 13 10 6 |
28 23 18 10 |
39 31 24 14 |
64 51 40 24 |
112 90 70 42 |
169 136 106 63 |
221 177 138 83 |
282 227 177 106 |
RHH*, RHW* RHW-2*, TW. THW, THHW THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 1 0 0 0 0 |
3 1 1 1 1 1 1 1 0 |
4 3 3 2 2 1 1 1 1 |
8 6 5 4 3 2 1 1 1 |
11 8 7 6 4 3 3 2 1 |
18 13 12 10 7 6 5 4 3 |
32 24 20 17 12 10 9 7 6 |
48 36 31 26 18 16 13 11 9 |
63 47 40 34 24 20 17 15 12 |
81 60 52 44 31 26 22 19 16 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
12 9 5 3 2 1 1 1 1 1 0 0 |
22 16 10 6 4 2 1 1 1 1 1 1 |
35 26 16 9 7 4 3 3 1 1 1 1 |
61 45 28 16 12 7 6 5 4 3 2 1 |
84 61 38 22 16 10 8 7 5 4 3 3 |
138 101 63 36 26 16 13 11 8 7 6 5 |
241 176 111 64 46 28 24 20 15 12 10 8 |
364 266 167 96 69 43 36 30 22 19 16 13 |
476 347 219 126 91 56 47 40 29 25 20 17 |
608 443 279 161 116 71 60 51 37 32 26 22 |
MAXIMUM NUMBER OF CONDUCTORS IN RIGID PVC CONDUIT, SCHEDULE 40 | |||||||||||
Trade Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
8 6 4 2 |
14 11 8 4 |
24 18 13 7 |
42 32 24 13 |
57 44 32 18 |
94 72 54 30 |
135 103 77 43 |
209 160 119 66 |
230 115 160 89 |
361 277 206 115 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
5 4 3 1 |
9 8 6 3 |
16 12 10 6 |
28 22 17 10 |
38 30 24 14 |
63 50 39 23 |
90 72 56 33 |
139 112 87 52 |
186 150 117 70 |
240 193 150 90 |
TW, THW, THHW, THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 0 0 0 0 0 |
2 1 1 1 1 1 1 1 0 |
4 3 3 2 1 1 1 1 1 |
8 6 5 4 3 2 1 1 1 |
11 8 7 6 4 3 3 2 1 |
13 13 11 10 7 6 5 4 3 |
26 19 16 14 10 8 7 6 5 |
40 30 25 22 15 13 11 9 8 |
53 40 34 29 20 17 15 12 10 |
69 51 44 37 26 22 19 16 13 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
11 8 5 3 1 1 1 1 1 1 0 0 |
21 15 9 5 4 2 1 1 1 1 1 1 |
34 25 15 9 6 4 3 3 1 1 1 1 |
60 43 27 16 11 7 6 5 3 3 2 1 |
82 59 37 21 15 9 8 7 5 4 3 3 |
135 99 62 36 26 16 13 11 8 7 6 5 |
193 141 89 51 37 22 19 16 12 10 8 7 |
299 218 137 79 57 35 30 25 18 15 13 11 |
401 293 184 106 77 47 40 33 24 21 17 14 |
517 377 238 137 99 61 51 43 32 27 22 18 |
MAXIMUM NUMBER OF CONDUCTORS IN RIGID PVC CONDUIT, SCHEDULE 80 | |||||||||||
Trade Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
8 5 3 1 |
11 9 6 3 |
20 15 11 6 |
35 27 20 11 |
49 38 28 15 |
82 63 47 26 |
118 91 67 37 |
185 142 106 59 |
250 192 143 79 |
324 248 185 103 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
4 3 2 1 |
8 6 5 3 |
13 10 8 5 |
23 19 15 9 |
32 26 20 12 |
55 44 34 20 |
79 63 49 29 |
123 99 77 46 |
166 133 104 62 |
215 173 135 81 |
RHH*, RHW RHW-2, TW, THW, THHW, THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 0 0 0 0 0 |
1 1 1 1 1 1 1 0 0 |
3 3 2 1 1 1 1 1 1 |
7 5 4 3 2 1 1 1 1 |
9 7 6 5 3 3 3 2 1 |
16 12 10 8 6 5 4 3 3 |
22 17 14 12 8 7 6 5 4 |
35 26 22 19 13 11 10 8 7 |
48 35 30 26 18 15 13 11 9 |
62 46 39 33 23 20 17 14 12 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
9 6 4 2 1 1 1 1 0 0 0 0 |
17 12 7 4 3 1 1 1 1 1 1 1 |
28 20 13 7 5 3 3 2 1 1 1 1 |
51 37 23 13 9 6 5 4 3 2 1 1 |
70 51 32 18 13 8 7 6 4 3 3 2 |
118 86 54 31 22 14 12 10 7 6 5 4 |
170 124 78 45 32 20 17 14 10 9 7 6 |
265 193 122 70 51 31 26 22 16 14 11 9 |
358 261 164 95 68 42 35 30 22 18 15 13 |
464 538 213 123 89 54 46 39 29 24 20 17 |
MAXIMUM NUMBER OF CONDUCTORS IN RIGID METAL CONDUIT | |||||||||||
Trade Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
9 7 5 3 |
15 12 9 5 |
25 19 14 8 |
44 33 25 14 |
59 45 34 19 |
98 75 56 31 |
140 107 80 44 |
216 165 123 68 |
288 221 164 91 |
370 284 212 118 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
6 5 3 1 |
10 8 6 4 |
17 13 10 6 |
29 23 18 11 |
39 32 25 15 |
65 52 41 24 |
93 75 58 35 |
143 115 90 54 |
191 154 120 72 |
246 198 154 92 |
RHH*, RHW RHW-2, TW, THW, THHW, THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 1 0 0 0 0 |
3 1 1 1 1 1 1 1 0 |
5 3 3 2 1 1 1 1 1 |
8 6 5 4 3 2 2 1 1 |
11 8 7 6 4 3 3 2 1 |
18 14 12 10 7 6 5 4 3 |
27 20 17 14 10 8 7 6 5 |
41 31 26 22 15 13 11 9 8 |
55 41 35 30 21 18 15 13 10 |
71 53 45 38 27 23 19 16 14 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
13 9 6 3 2 1 1 1 1 1 0 0 |
22 16 10 6 4 2 1 1 1 1 1 1 |
36 26 17 9 7 4 3 3 1 1 1 1 |
63 46 29 16 12 7 6 5 4 3 2 1 |
85 62 39 22 16 10 8 7 5 4 3 3 |
140 102 64 37 27 16 14 11 8 7 6 5 |
200 146 92 53 38 23 20 17 12 10 8 7 |
309 225 142 82 59 36 31 26 19 16 13 11 |
412 301 189 109 79 48 41 34 25 21 18 15 |
531 387 244 140 101 62 53 44 33 27 23 19 |
MAXIMUM NUMBER OF CONDUCTORS IN FLEXIBLE METAL CONDUIT | |||||||||||
Trade Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
9 7 5 3 |
15 11 8 5 |
23 18 13 7 |
36 28 21 11 |
53 41 30 17 |
94 72 54 30 |
141 108 81 45 |
203 156 116 64 |
277 212 158 88 |
361 277 207 115 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
6 5 4 1 |
10 8 6 4 |
15 12 10 6 |
24 19 15 9 |
35 28 22 13 |
62 50 39 23 |
94 75 59 35 |
135 108 85 51 |
184 148 115 69 |
240 193 151 90 |
RHH*, RHW RHW-2, TW, THW, THHW, THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 1 0 0 0 0 |
3 1 1 1 1 1 1 1 0 |
4 3 3 2 1 1 1 1 1 |
7 5 4 4 2 1 1 1 1 |
10 7 6 5 4 3 3 2 1 |
18 13 11 10 7 6 5 4 3 |
27 20 17 14 10 9 7 6 5 |
39 29 25 21 15 12 10 9 7 |
53 39 34 29 20 17 14 12 10 |
69 51 44 37 26 22 19 16 13 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
13 9 6 3 2 1 1 1 1 1 0 0 |
22 16 10 6 4 2 1 1 1 1 1 1 |
33 24 15 9 6 4 3 3 1 1 1 1 |
52 38 24 14 10 6 5 4 3 2 1 1 |
76 56 35 20 14 9 7 6 4 4 3 2 |
134 98 62 35 25 16 13 11 8 7 6 5 |
202 147 93 53 38 24 20 17 12 10 9 7 |
291 212 134 77 55 34 29 24 18 15 12 10 |
396 289 182 105 76 46 39 33 24 20 17 14 |
518 378 238 137 99 61 51 43 32 27 22 18 |
MAXIMUM NUMBER OF CONDUCTORS IN LIQUIDTIGHT FLEXIBLE METAL CONDUIT | |||||||||||
Trade Sizes In Inches | |||||||||||
Type Letters |
Cond. Size AWG/kcmil |
1/2 | 3/4 | 1 | 1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 3 1/2 | 4 |
TW, THHW, THW, THW-2 |
14 12 10 8 |
9 7 5 3 |
15 12 9 5 |
25 19 14 8 |
44 33 25 14 |
57 43 32 18 |
93 71 53 29 |
140 108 80 44 |
215 165 123 68 |
280 215 160 89 |
365 280 209 116 |
RHH*, RHW* RHW-2* |
14 12 10 8 |
6 5 3 1 |
10 8 6 4 |
16 13 10 6 |
29 23 18 11 |
38 30 23 14 |
62 50 39 23 |
93 75 58 35 |
143 115 89 53 |
186 149 117 70 |
243 195 152 91 |
RHH*, RHW RHW-2, TW, THW, THHW, THW-2 |
6 4 3 2 1 1/0 2/0 3/0 4/0 |
1 1 1 1 1 0 0 0 0 |
3 1 1 1 1 1 1 1 0 |
5 3 3 2 1 1 1 1 1 |
8 6 5 4 3 2 2 1 1 |
11 8 7 6 4 3 3 2 1 |
18 13 11 9 7 6 5 4 3 |
27 20 17 14 10 8 7 6 5 |
41 30 26 22 15 13 11 9 8 |
53 40 34 29 20 17 15 12 10 |
70 52 44 38 26 23 19 16 13 |
THHN, THWN, THWN-2 |
14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 |
13 9 6 3 2 1 1 1 1 1 0 0 |
22 16 10 6 4 2 1 1 1 1 1 1 |
36 26 16 9 7 4 3 3 1 1 1 1 |
63 46 29 16 12 7 6 5 4 3 2 1 |
81 59 37 21 15 9 8 7 5 4 3 3 |
133 97 61 35 25 15 13 11 8 7 6 5 |
201 146 92 53 38 23 20 17 12 10 8 7 |
308 225 141 81 59 36 30 26 19 16 13 11 |
401 292 184 106 76 47 40 33 25 21 17 14 |
523 381 240 138 100 61 52 44 32 27 23 19 |
MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTORS FOR GROUNDING RACEWAY AND EQUIPMENT
RATING OR SETTING OF AUTOMATIC OVERCURRENT DEVICE IN CIRCUIT AHEAD OF EQUIPMENT, CONDUIT. ETC.. NOT EXCEEDING (AMPERES) | SIZE COPPER |
15 20 30 40 60 100 200 300 400 500 |
14 12 10 10 10 8 6 4 3 2 |
GROUNDING ELECTRODE CONDUCTOR FOR ALTERNATING-CURRENT SYSTEMS
SIZE OF LARGEST UNGROUNDED SERVICEENTRANCE CONDUCTOR OR EQUIVALENT AREA FOR PARALLEL CONDUCTORS* | SIZE OF GROUNDING ELECTRODE CONDUCTOR |
COPPER | COPPER |
2 OR SMALLER 1 OR 1/0 2/0 OR 3/0 OVER 3/0 THRU 350kcmil OVER 350 kcmil THRU 600 kcmil OVER 600 kcmil THRU 1100 kcmil OVER 1100 kcmil |
8 6 4 2 1/0 2/0 3/0 |